2-channel relay module with power measurement and voltage control WB-MRWM2
- FCA – you pick up from us
- DAP – we deliver, you do customs in your country and
- DDP – we deliver and we do customs clearance
2-Channel Relay Module with Power Measurement and Voltage Control WB-MRWM2
Designed for switching general-purpose loads up to 4.5 kW, including inductive loads: outlet groups, motors, heaters, etc.
Measures voltage and active power on each output. Protects loads from unacceptable voltage fluctuations.
Rated current: 20 A, inrush current: up to 80 A (20 ms). 2 relay outputs, 2 discrete inputs.
Advantages
- Powerful relays.
- Voltage and active power measurement on each output.
- Protective load disconnection when the voltage goes out of the allowed limits.
- Protective startup delay and restart delay.
- Recognition of button presses on inputs and flexible configuration of the response of outputs to presses, which allows you to control one or more outputs from any inputs.
- Indication of output status, power consumption and voltage error on the housing for quick diagnostics during commissioning.
- Pulse counting and frequency measurement at inputs.
- Safe mode in case of RS-485 communication failure.
- Output timer functions: on and off delay, switching on for a set time, cyclic mode.
- Programmable protection against bounce of switch contacts.
- Compact housing for DIN rail.
- Fast and easy integration into automation and monitoring systems.
- Technical support on the portal.
- Your company logo can be applied.
Supports Fast Modbus ⚡, which allows you to instantly deliver input states and button press counter values to the Wiren Board controller.
Hardware
- 2 relay channels rated 20 A 230 V AC.
- Maximum switching current: 26 A per channel.
- Maximum inrush current: up to 80 A (20 ms).
- 2 discrete inputs with group galvanic isolation; by default, each input controls the output with the same number.
- Press handling: short, long, double and short, then long.
- Voltage and active power measurement on each output; outputs can be connected to different phases.
- Power measurement error: 2 % in the range of 20…100 % of rated power.
- Voltage measurement error: 2 % at 230 V.
- Voltage control limits: lower 120…220 V, upper 230…277 V, configurable for each output.
- Supply voltage: 9…28 V direct current.
- Measuring circuit supply voltage: 120…277 V alternating current.
- Interface: RS-485, Modbus RTU.
- Operating temperature: -40…+80 °C.
- DIN rail housing, 3 modules (53 x 90 x 58 mm).
Hongfa Long Life Relays
Reliable Hongfa relays are used for switching. The relays have silver tin oxide contacts (AgSnO2), which ensures resistance to high currents. Therefore, the WB-MRWM2 module is well suited for switching powerful inductive loads.
To make sure of the relay quality, we tested them with inrush currents several times higher than the rated ones.
The relay manufacturer claims a service life of at least 30 000 operations.
Local control
Flexible configuration of the response of outputs to button presses allows you to use the module for local control of loads and implement simple logic without contactors and intermediate relays. This is convenient in small installations where there is no controller and no possibility to install an RS-485 bus.
If the module is connected to a bus, local logic can be combined with commands from the controller. The interaction of inputs and outputs is configured in the web interface of the Wiren Board controller or by writing to Modbus registers, and the settings are stored in the module memory.
Safe mode
If the module is installed at a distance from the switchboard and connected to the RS-485 bus, then there is a risk of loss of control from the head unit. In order not to lose control over an important technological process, the module has a safe mode that allows you to switch the relay outputs to a specified state.
For each output, you can configure its own safe state and the need to switch to it in case of loss of communication. In addition, you can enable or disable control from inputs in safe mode, for example, prohibit control from buttons when communication with the device is lost.
Fast Modbus support
All Wiren Board devices, in addition to the standard Modbus RTU, can work with its extension Fast Modbus ⚡, which adds new features:
- instant polling of input states and measured values via events;
- quick search for devices connected to the controller;
- resolving address collisions on the bus.
For the user, the additional features are enabled seamlessly: if the device supports the extension, the controller driver will work with it via Fast Modbus; if the device knows nothing about the extension, it will work via standard Modbus RTU.
Quality control at each stage of production
We develop and manufacture all Wiren Board devices ourselves. Also everyone devices undergo multi-stage quality control:
- During development - checking the components used for compliance with the declared ones characteristics and testing of the prototype device at extreme operating conditions.
- After installation of SMD components - automated optical control.
- After soldering the lead components - visual inspection of soldering.
- After assembling the device, functional testing on an automated stand.
- When shipped to the warehouse - control of completeness, stickers, appearance.
Thanks to this approach, the failure rate is no more than 0.5% of all released devices.
If the device fails within two years from the date of purchase, we will replace it for free without need to be sent to a service center.
Setup
When used with a Wiren Board controller, you can use the mouse in the web interface:
- Enable and disable channels and configure the polling period.
- Set input operating modes.
- Configure the reaction of outputs to inputs.
- Set the state of the outputs when power is applied.
- Configure safe mode settings.
- Adjust the contact bounce protection time.
- Configure voltage control and protective delays.
- Configure output timer functions.
For configuration without a controller, you can use the Wiren Board Device Editor paired with a WB-USB485 interface converter or a similar device.
When used with other equipment, the module can be configured via the RS-485 bus by writing values to Modbus registers. The register table is open, well documented and available online in the device documentation.
Reading the readings
If a Wiren Board controller is used, then the states of inputs, outputs and button press counters, the measured voltage, power and active energy for each channel, as well as the voltage control status, are available in the controller's web interface and can be used in automation scripts or transferred to a higher-level system. The device card displays only the channels enabled in the polling settings.
The module also transmits all data via Modbus RTU (RS-485), which can be read by any equipment or software that supports this protocol: third-party controllers, HMI panels or SCADA.
Brand Wiren Board